• Circuit Breaker Terms and Definitions

    Quick reference of over 150 circuit breaker terms and acronyms.


    accessory — Electrical or mechanical device that performs a secondary or minor function apart from overcurrent protection.

    accessory cover — Removable cover on the front of a circuit breaker behind which are mounted the trip unit and all electrical accessories.

    adjustable rating plug — Component which plugs into the trip unit, establishing the ampere rating of a circuit breaker

    AIC — Amperes interrupting capacity.

    AIR — Amperes interrupting rating.

    alarm switch — See bell alarm and overcurrent trip switch.

    ambient compensation — Limits or eliminates thermal derating (lowering of capabilities) caused by extreme ambient temperatures.

    ambient temperature — Refers to the temperature of the air immediately surrounding the circuit breaker/protection device.

    ambient temperature rating — Temperature at which the continuous current rating (handle rating) of a circuit breaker is based; the temperature of the air immediately surrounding the circuit breaker which can affect the thermal (overload) tripping characteristics of thermal-magnetic circuit breakers. Electronic trip circuit breakers, however, are insensitive to normal (-10° to 50°C) ambient conditions.

    ammeter — (local current meter) A module that mounts directly to a circuit breaker trip unit and reports RMS phase and ground-fault current values as seen by the trip unit.

    ampacity — The current, in amperes, that a conductor or circuit breaker can carry continuously under the conditions of use without exceeding its temperature rating.

    ampere — The equivalent of one coulomb per second or the steady current produced by one volt applied across a resistance of one ohm.

    Back to Top

    amperes interrupting rating — The highest current at rated voltage that an overcurrent protective device is intended to interrupt under specified test conditions (NEC).

    ANSI — American National Standards Institute.

    arcing contact — Contacts designed to prevent the main contacts from being damaged. When the circuit breaker opens, the main contacts part first and then the arcing contacts part, drawing the arc across them. When the circuit breaker closes, the arcing contacts make first, again drawing the arc across them. This prevents the main contacts from carrying the arc and preserves them.

    automatic molded case switch — A switch with construction similar to a molded case circuit breaker except that the switch opens only instantaneously at a non-adjustable trip point calibrated to protect only the molded case switch itself.

    automatic reset — Device that will automatically open an overload circuit. It will also automatically close or complete the circuit after a period of time. If the overload is still present, the device will continue to cycle until either the power or the overload is removed.

    auxiliary switch — A switch mechanically operated by the main device for signaling, interlocking, or other purposes.

    bell alarm — Mechanically-operated switch used to indicate the main contact position of a circuit breaker, which indicates when a circuit breaker has tripped. Also see overcurrent trip switch.

    blowout coil — A coil, carrying an electric current, that serves to deflect and thus extinguish an arc formed when the contacts of a switch part to turn off the current.

    BPFE — Electrical closing push button.

    branch circuit — The circuit between the final overcurrent device protecting the circuit and the outlet(s).

    BCM — Circuit breaker communications module.

    Back to Top

    CSA — (Canadian Standards Association) Canadian product safety testing and certification organization.

    carriage — See cradle.

    CCM — Cradle communication module.

    charging handle — See spring charging handle.

    circuit breaker — A device designed to open and close a circuit by nonautomatic means and to open the circuit automatically on an overcurrent without damage to itself when properly applied within its rating.

    circuit breaker communications module — (BCM) = A module which, when installed in a circuit breaker, receives and transmits information on a communication network.

    circuit breaker frame — (1) The circuit breaker housing which contains the current carrying components, the current sensing components, and the tripping and operating mechanism. (2) That portion of an interchangeable trip molded case circuit breaker remaining when the interchangeable trip unit is removed.

    close button — A button for manually closing the main contacts after the closing springs are charged.

    close button cover — A cover which fits over the close button and blocks access to it. Access to the close button may be permitted through the use of a tool or rod inserted through a small hole in the front of the close button cover.

    closing coil — (shunt close) = A coil which closes a circuit breaker electrically using an external voltage source when a specified voltage is applied across the coil.

    coil clearing switch — Mmechanically-operated switch in series with the coil of a shunt trip device which breaks the coil current when a circuit breaker opens.

    Back to Top

    communication network — A network allowing the flow of information between electrical components, comprised of programmable controller interface units, protocol software and modems.

    conductor — Substance or body that allows a current of electricity to pass continuously along it.

    continuous current rating — (handle rating) (ampere rating) The designated RMS alternating or direct current in amperes which a device or assembly will carry continuously in free air without tripping or exceeding temperature limits.

    continuous load — A load where the maximum current on the circuit is expected to continue.

    cradle communications module — (CCM) An external module which allows addressing of the cradle and retention of the address when the drawout circuit breaker is in the disconnected position and which is used to transmit information about the position of a circuit breaker in the cradle to the communication network.

    cradle compartment — A compartment containing all connectors, shields, adapters, barriers, spreaders, shutters, keys and interlocking devices for a drawout circuit breaker.

    CT — Current transformer. See also cell switch.

    current path — (of a circuit breaker) The current-carrying conductors within a circuit breaker between, and including, line and load terminations.

    current transformer — (current sensor) (CT) An instrument to measure current, encircling a conductor carrying the current to be measured or controlled.

    dead tank — Dead tank breakers have grounded tanks, unlike Live tank breakers which use the insulating column to house the mechanism and contact assemblies.

    demand metering — The metering of power or current demand seen by a circuit breaker. It is calculated over a fixed or sliding time window that can be programmed from five to 60 minutes. Depending on the contract signed with the power supplier, specific programming makes it possible to avoid or minimize the cost of overrunning the subscribed power. Maximum demand values are systematically stored and time stamped.

    Back to Top

    disconnecting contacts — See main disconnecting contacts and secondary disconnecting contacts.

    drawout circuit breaker — An assembly of a circuit breaker and a supporting structure (cradle) so constructed that the circuit breaker is supported and can be moved to either the main circuit connected or disconnected position without removing connections or mounting supports.

    drawout mechanism — A mechanism which engages the drawout cradle assembly and draws a circuit breaker into or out of a switchboard. The drawout mechanism includes the drawout mechanism shaft, drawout levering device arms and a drawout position indicator.

    drawout position indicator — An indicating means which shows the position of a circuit breaker in the drawout structure.

    drawout access cover — (drawout shaft cover) A shutter which allows or restricts access to the drawout shaft.

    electrical closing push button — A push button used to electrically close a circuit breaker using a shunt close with communication option. This takes into account all safety functions that are part of the control and monitoring system of the installation.

    electrical operator — (motor operator) An electrical device used to open and close a circuit breaker or switch and reset a circuit breaker. See also spring charging motor.

    electronic trip circuit breaker — A circuit breaker which uses current sensors and electronic circuitry to sense, measure and respond to current levels.

    fixed-mounted circuit breaker — A circuit breaker so mounted that it cannot be removed without removing primary and sometimes secondary connections and/or mounting supports.

    frame size — The largest ampere rating available in a group of circuit breakers of similar physical configuration.

    frequency — The number of cycles per second for an alternating current system.

    Back to Top

    frequency rating — The range of frequencies within which a product can be applied.

    ground fault — An unintentional current path, through ground, back to the source.

    ground-fault delay — The length of time a circuit breaker trip unit will delay before initiating a trip signal to the circuit breaker after a ground fault has been detected.

    ground-fault module — An electronic accessory used in combination with thermal-magnetic circuit breakers to provide branch circuit ground-fault protection and ground-fault indication.

    ground-fault pickup — The level of ground-fault current at which the trip system begins timing.

    handle rating — See continuous current rating.

    IDMTL — Long-time delay curve which can be varied in slope to enhance selectivity.

    IEC — International Electrotechnical Commission.

    IEEE — Institute of Electrical and Electronics Engineers.

    Ig — Ground-fault pickup.

    Ii — Instantaneous pickup.

    Back to Top

    In — Sensor rating.

    individually-mounted circuit breaker — A circuit breaker so mounted that it cannot be removed without removing primary and sometimes secondary connections and/or mounting supports.

    instantaneous pickup — The current level at which a circuit breaker will trip with no intentional time delay.

    instantaneous trip — A qualifying term indicating that no delay is purposely introduced in the tripping action of a circuit breaker during short-circuit conditions.

    insulated case circuit breaker — (ICCB) = UL Standard 489 Listed nonfused molded case circuit breakers which utilize a two-step stored energy closing mechanism, electronic trip system and drawout construction.

    integral ground-fault protection for equipment — Equipment ground-fault protection on grounded neutral systems provided by components internal to a circuit breaker.

    interchangeable trip unit — A trip unit which can be interchanged by a user among circuit breaker frames of the same design.

    interrupting rating — The highest current at rated voltage available at the incoming terminals of a circuit breaker. When a circuit breaker can be used at more than one voltage, the interrupting rating will be shown on the circuit breaker for each voltage level. The interrupting rating of a circuit breaker must be equal to or greater than the available short-circuit current at the point at which the circuit breaker is applied to the system.

    inverse time — A qualifying term indicating there is purposely introduced a delay in the tripping action of a circuit breaker, which delay decreases as the magnitude of the current increases.

    Ir — Long-time pickup.

    Isd — Short-time pickup.

    Back to Top

    I2t — See let-through current.

    I2t IN — (I2t ON) An inverse time delay characteristic.

    I2t OUT — (I2t OFF) A constant time delay characteristic.

    latch check switch — A mechanically-operated switch which senses if the trip latch is reset.

    let-through current — The peak current (measured in amperes) which passes through an overcurrent protective device during an interruption.

    let-through I2t — An expression related to energy (measured in ampere-squared seconds) which passes through an overcurrent protective device during an interruption.

    LI — A combination of adjustable trip functions including long-time ampere rating, long-time delay, and instantaneous pickup.

    lifting adapter — A device used with a crane, chain block or an optional lifting mechanism supplied with switchgear for removing and installing a drawout circuit breaker or fuse truck.

    LIG — A combination of adjustable trip functions including long-time ampere rating, long-time delay, instantaneous pickup, ground-fault pickup and ground-fault delay.

    limit switch — A switch mechanically operated by the motion of a machine part or presence of an object.

    live tank — Live tank breakers use the insulating column to house the mechanism and contact assemblies, so they are energized at system voltage (live). Dead tank breakers have grounded tanks.

    Back to Top

    local current meter — An ammeter installed as part of a trip unit.

    long-time ampere rating — An adjustment which, in combination with the installed rating plug, establishes the continuous current rating of a fullfunction electronic trip circuit breaker.

    long-time delay — The length of time a circuit breaker will carry a sustained overcurrent (greater than the long-time pickup) before initiating a trip signal.

    long-time pickup — The current level at which a circuit breaker's long-time delay function begins timing.

    low-voltage power circuit breaker — (LVPCB) A circuit breaker tested to ANSI C37 Standards with a two-step stored-energy mechanism, an electronic trip system, and drawout construction.

    LS — A combination of adjustable trip functions including long-time ampere rating, long-time delay, short-time pickup, short-time delay and a defeatable instantaneous pickup.

    LSG — A combination of adjustable trip functions including long-time ampere rating, long-time delay, short-time pickup, short-time delay, defeatable instantaneous pickup, ground-fault pickup and ground-fault delay.

    LSI — A combination of adjustable trip functions including long-time ampere rating, long-time delay, short-time pickup, short-time delay and defeatable instantaneous pickup.

    LSIG — A combination of adjustable trip functions including long-time ampere rating, long-time delay, short-time pickup, short-time delay, defeatable instantaneous pickup, ground-fault pickup and ground-fault delay.

    main disconnecting contacts — Spring-loaded and self-aligning contact located on the rear of a drawout circuit breaker that provides positive electrical contact when the circuit breaker is in the connected position.

    MCH — Spring-charging motor.

    Back to Top

    MDGF — Modified differential ground-fault system.

    manual charging handle — A manually-operated handle which charges the closing springs of a circuit breaker.

    manual reset — Refers to breakers in which the electrical contacts remain open after a trip until someone physically closes or completes the circuit by either pushing a reset button or throwing a switch

    maximum ultimate trip — (must trip) Current rating at which a circuit protection device will trip within a certain period of time at a specified temperature.

    mechanical operation counter — (CDM) A mechanical device which indicates the total number of circuit breaker operating cycles.

    miniature circuit breaker — (MCB) A small circuit breaker which is assembled as an integral unit in a supportive and enclosed housing of insulating material that is rated 150A or less and is used in 120V, 120/240V, 240V and 480Y/277V ac systems and dc systems up to 125Vdc.

    minimum ultimate trip — (must hold) Current rating for which a circuit protection device will not trip for an extended period of time at a specified temperature.

    MN — Undervoltage release.

    molded case circuit breaker — (MCCB)A circuit breaker which is assembled as an integral unit in a supportive and enclosed housing of insulating material, generally 20-3000A in ampacity and used in systems up to 600Vac and 500Vdc.

    motor circuit protector — A recognized component of construction similar to a circuit breaker except with no thermal elements so that it provides short-circuit protection only.

    MX — Shunt trip.

    Back to Top

    nuisance trips — Trips caused by a response to non-damaging inrush or start-up current surges, as opposed to an actual overcurrent trip.

    neutral current transformer — A current transformer which encircles a neutral conductor; required on circuit breakers with ground-fault protection, when applied on a grounded system.

    OF — Auxiliary switch.

    open/closed indicator — Displays the position of a circuit breaker's main contacts (open or closed).

    operating mechanism — An internal mechanical system which opens and closes circuit breaker contacts.

    OTS — Overcurrent trip switch (alarm switch, bell alarm). A mechanical switch that operates when a circuit breaker is tripped by the overcurrent protection system.

    overcurrent — Any current in excess of the rated continuous current of equipment or the ampacity of a conductor.

    overcurrent mechanism — An internal mechanical system which trips a circuit breaker during an overcurrent.

    overcurrent protection — Protection achieved by limiting the duration and magnitude of exposure to an overcurrent.

    overcurrent trip element — A device which detects an overcurrent and transmits the energy necessary to open the circuit automatically (UL only).

    overcurrent trip switch — (SDE) = A mechanically-operated switch which indicates when a circuit breaker has tripped due to overcurrent conditions.

    Back to Top

    overload — An electrical load or current flow greater than that which a circuit is designed to handle.

    overload capacity — The highest level of overload current that devices will interrupt and remain in operable condition, capable of clearing additional overloads.

    overload delay — The length of time a circuit breaker will carry a sustained low-level overcurrent before initiating a trip signal.

    peak current sensing — A method of determining electrical current by means of detecting the current peaks.

    peak let-through current — The maximum peak current flowing in a circuit during an overcurrent condition.

    PF — A switch used to indicate that a circuit breaker is ready to close.

    phase barrier — A barrier which provides phase-to-phase or phase-to-ground isolation.

    primary disconnect contacts — An electrical plug-on connector in the main current path between the drawout components and the cradle mounted in a switchboard or switchgear cubicle.

    puffer tube — Used on high voltage circuit breakers to blow air across the main contacts during a trip operation. The air helps cool and de-ionize the gas in the contact gap, resulting in rapid dielectric recovery. The air can be compressed in a cylinder by the contact motion.

    push-to-close button — A button for manually closing the main contacts after the closing springs are charged.

    push-to-open button — A button for manually opening a circuit breaker.

    Back to Top

    push-to-trip button — A button for manually tripping a circuit breaker.

    racking device shutter — See drawout shaft cover.

    racking interlock — Prevents the racking of a drawout circuit breaker when the enclosure door is open by not allowing the racking crank to be inserted into the circuit breaker.

    rating plug — A component which plugs into an electronic trip unit, establishing the maximum continuous current rating of a circuit breaker.

    RES — (remote reset after fault) A component which resets an overcurrent trip switch (SDE) and the mechanical operator after tripping.

    residual ground-fault sensing — A means of providing equipment ground-fault protection utilizing sensors on each individual phase.

    RMS — Root-mean-square.

    RMS current sensing — A method of determining the true RMS current of sinusoidal and non-sinusoidal waveforms by sampling the current waveform a number of times per cycle, then calculating the true RMS value.

    safety factor — The allowance added to the steady-state application current to ensure that the protective device selected will be more than sufficient to handle the application without nuisance trips.

    safety shutter — A device that closes to block access to the line bus when a circuit breaker is in the disconnected, test or withdrawn position.

    SDE — Overcurrent trip switch.

    Back to Top

    secondary disconnect contacts — An electrical plug-on connector in the secondary (control) circuit between a drawout circuit breaker and its cradle in the switchboard or switchgear.

    sensor — The current sensing element within a circuit breaker which provides the sensing function for that circuit breaker.

    sensor plug — A component used to set the sensor size of a circuit breaker.

    sensor size — Maximum ampere rating possible for a specific circuit breaker, based on the size of the current sensor inside the circuit breaker. Sensor size is less than or equal to frame size.

    SGR — Source ground return system.

    short-circuit delay — (STD) The length of time that a circuit breaker will carry a current greater than the short-circuit pickup before initiating a trip signal.

    short-circuit pickup — The current level at which a the short-circuit delay function begins timing.

    short-time delay — The length of time that a circuit breaker will carry a current greater than the short-time pickup before initiating a trip signal.

    short-time pickup — The current level at which the short-time delay function begins timing.

    shunt close — (closing coil) (XF) An accessory that closes a circuit breaker from a remote location using an external voltage source.

    shunt trip — (MX) An accessory that trips a circuit breaker from a remote location using an external voltage source.

    Back to Top

    spring-charging handle — A handle located on the front of a circuit breaker used to manually charge the stored energy mechanism.

    spring charging motor — A motor which electrically charges a circuit breaker's stored energy closing spring(s).

    STD — Short-time delay.

    stored energy mechanism — A spring mechanism that is compressed (or charged) and then released (or discharged) to close a circuit breaker.

    terminal block — The connection points for control wiring on a circuit breaker.

    tg — Ground-fault delay.

    thermal imaging — A trip unit function that accurately maps the heating and cooling effects of load behavior on rated conductors to provide thermal protection without nuisance tripping.

    thermal-magnetic circuit breaker — A general purpose term for circuit breakers that use bimetals and electromagnetic assemblies to provide both thermal and magnetic overcurrent protection.

    thermal memory — Provides continuous temperature rise status of wiring for a period of time both before and after a device trips. This allows circuit breaker's to respond to a series of overload conditions which would otherwise go undetected.

    tr — Long-time delay.

    tsd — Short-time delay.

    Back to Top

    transformer — A static device with primary winding, connected in series with a conductor carrying the current to be measured or controlled within the switchgear.

    trip button — See push-to-trip button.

    trip curve — A graphical representation of the response of a circuit breaker to current over a period of time.

    trip-free — A characteristic of certain breakers that provides independence between the protection mechanism and the operating button or handle, such that a fault cannot be maintained manually (or held closed) against an overload.

    trip indicator — A module that mounts directly to a trip unit and displays whether the circuit breaker tripped due to an overload, a short-circuit or a ground-fault condition.

    trip indicator reset — A button on a trip indicator module used to reset the trip indicator.

    trip unit — A programmable device which measures and times current flowing through a circuit breaker and initiates a trip signal when appropriate.

    UL — Underwriters Laboratories Inc.

    undervoltage trip release — (MN, UVR) An accessory which trips a circuit breaker automatically when the monitored circuit voltage falls below a predetermined percentage of its specified value.

    Underwriters Laboratories — An independent, not-for-profit standards development, product safety testing and certification organization.

    unit-mount circuit breaker — A circuit breaker mounted such that it cannot be removed without removing primary and sometimes secondary connections or mounting supports.

    Back to Top

    withstand rating — The level of RMS symmetrical current that a circuit breaker can carry with the contacts in a closed position for a stated period of time–usually stated in cycles.

    zero-sequence ground-fault sensing — A means of providing equipment ground-fault protection utilizing an external sensor (surrounding all phase and neutral conductors).

    zone-selective interlocking — (ZSI) A communication capability between electronic trip systems and ground-fault relays which permits a short circuit or ground fault to be isolated and cleared by the nearest upstream device with no intentional time delay.

    ZSI — Zone-selective interlocking.